AC Current Sensors

Catalog Download

Connect directly to any Data Logger input channel.  Also connects directly to any recorder or data acquisition system that has a 0-5vdc input.  No external power required.

Split core construction simplifies installation on existing conductor. Nylon thumb screws, no exposed metal parts; Monitor motors, pumps, or any AC load.

AC Current Sensor with 0-5vdc output
SC200 AC Current Sensor (0-200 amps)

Specifications - AC Current Sensors
Input Current AC Current, single phase, 50 - 400 Hz, load power factor 0.5 to 1.0 lead or lag.
Accuracy ±2.0% of reading from 2.5 % to 100% of full scale.

±4% of reading at 1% of full scale.

Bandwidth 10-1000Hz (within ±3db)
Temperature effect ±0.05% (-20 to 85°C)
Response time 250 milliseconds (input from 10% to 90% of full scale).
Ripple 0.5%
Voltage rating 600 Vac. Tested with full wave 10KV impulse for 60 seconds.
Overload 1.6x full scale (continuous).
Surge 3x full scale.
Lead wires 8 ft (2.4 meter) signal cable.
Output signal Linear 0 - 5vdc
Low range usability To below 0.1% of full scale.
Overall size Add 2" to Window size in table below for overall length and height dimension (Add 2.5" for SC1500A).

Overall width 1.25" (includes nylon thumbscrews)

 

Part No.

Range

Window Size

Price $US

SC100A 0-100 amps ac 0.5" square

595.00

SC200A 0-200 amps ac 1" square

695.00

SC500A 0-500 amps ac 2" square

1,350.00

SC1500A 0-1500 amps ac 2.5" square

1,550.00