Connect directly to any Data Logger input channel. Also connects directly to any recorder or data acquisition system that has a 0-5vdc input. No external power required.
Split core construction simplifies installation on existing conductor. Nylon thumb screws, no exposed metal parts; Monitor motors, pumps, or any AC load.

SC200 AC Current Sensor (0-200 amps)
| Specifications - AC Current Sensors | |
| Input Current | AC Current, single phase, 50 - 400 Hz, load power factor 0.5 to 1.0 lead or lag. |
| Accuracy | ±2.0% of reading from 2.5 % to 100% of full scale.
±4% of reading at 1% of full scale. |
| Bandwidth | 10-1000Hz (within ±3db) |
| Temperature effect | ±0.05% (-20 to 85°C) |
| Response time | 250 milliseconds (input from 10% to 90% of full scale). |
| Ripple | 0.5% |
| Voltage rating | 600 Vac. Tested with full wave 10KV impulse for 60 seconds. |
| Overload | 1.6x full scale (continuous). |
| Surge | 3x full scale. |
| Lead wires | 8 ft (2.4 meter) signal cable. |
| Output signal | Linear 0 - 5vdc |
| Low range usability | To below 0.1% of full scale. |
| Overall size | Add 2" to Window size in table below for overall length and height dimension (Add 2.5" for SC1500A).
Overall width 1.25" (includes nylon thumbscrews) |
|
Part No. |
Range |
Window Size |
Price $US |
| SC100A | 0-100 amps ac | 0.5" square |
595.00 |
| SC200A | 0-200 amps ac | 1" square |
695.00 |
| SC500A | 0-500 amps ac | 2" square |
1,350.00 |
| SC1500A | 0-1500 amps ac | 2.5" square |
1,550.00 |